MPF Fire Alarm System
Model: MPF Fire Alarm System
Model |
FAS-R |
Capacity |
1 ~8 loops, up to 300 sensors and modules per loop |
Input power |
AC220V,50 Hz |
Battery power |
DC24V 4Ah at least |
Resistance of cable |
Resistance of signaling wire <20Ω; insulation resistance >2MΩ@500V |
Alarm delay time |
0 ~ 40 seconds |
Operating temp/ humidity |
0°C ~ 50°C,relative humidity <95% (non-condensing) |
Material of case |
Steel, 1.2mm thickness |
Dimensions |
1~4 loops: 500x600x150 ; 5~8 loops: 500x1000x150 (WxHxD, mm) |
Optional |
Thermal printer, Custom graphics, Voice evacuation, Remote annunciator |
Model |
FR-G |
Operating Voltage |
DC18V ~ 30V |
Monitor current |
1.5mA (typical) @ DC24V |
Alarm current |
12mA (maximum) @ DC24V |
LED indications |
Normal: flash one time per 6 seconds; Alarm: always on; Failure: flash two times per 6 seconds |
EOL resistor |
10KΩ,1/4W |
Operating temperature |
0°C ~ 50°C, |
Relative humidity |
< 95% RH, non-condensing |
Dimensions |
60x76x32 (WxHxD, mm) |
Model |
FD-S |
Operating Voltage |
DC 18V ~ 30V |
Quiescent current |
1.7 mA / DC 24V |
Alarm current |
15mA / DC 24V |
Alarm response threshold |
15% during 30 seconds |
LED indicator |
Normal: flash one time per 6 seconds; Alarm: always on; Failure: flash two times per 6 seconds |
Operating temperature |
0°C ~ 50°C, |
Relative humidity |
< 95% RH, non-condensing |
Material / color |
Fire-proof plastic / White |
Dimensions |
Φ102 x 52 mm |